HLP-A Series
HLP-A Series
-
45
-
CD050 Multi-input 1 (FOR function)
Factory Setting: 02
CD051 Multi-input 2 (REV function)
Factory Setting: 03
CD052 Multi-input 3 (RST function)
Factory Setting: 10
CD053 Multi-input 4 (SPH function)
Factory Setting: 17
CD054 Multi-input 5 (SPM function)
Factory Setting: 18
CD055 Multi-input 6 (SPL function)
Factory Setting: 19
Set Range: 00—32 Unit: No
00: Invalid.
The terminal is set for empty to prevent false actions.
01: RUN
Running. It can be combined with other terminals to
compose multiple control modes.
02: FOR
Forward Rotation
03: REV
Reverse Rotation
04: STOP
Stopping
05: FOR/REV
Switching of FOR/REV rotation
06: JOG
Jogging
07: Jog FOR Rotation
08: Jog REV Rotation
09: Emergent Stop: Emergent stop. It can receive external emergent stop
command or other fault signals
10: RST
Reset. This terminal can be used for reset af ter a fault is
removed.
11: Reserved
12: Over-heat of heat sink or motor: This contact can be used to detect over-heat
of the heat sink or motor to protect the motor and inverter.
13: External Control Timer 1 Start: When the contact is closed, the timer will
start and begin to count time. When the timer reaches the
set point the corresponding multi-inputs will act.
14: External Control Timer 2 Start
15~16: Reserved
17: High speed
High, middle and low speed can compose three kinds of
operation mode
18: Middle speed with different frequencies. In the three terminals the high-
end signal has
19: Low speed
priority. Low, Middle and High Speed are determined
respectively by Frequency 2, 3, 4.
20: Multi-speed 1 7-speed setting can be composed through Multi-speed 1, 2, 3.
21: Multi-speed 2
22: Multi-speed 3
23: Ramp Time 1: This terminal can be used to select the ramp time of the
inverter.
24: Ramp Time 2: 4 kinds of ramp time are available for choice.
25: UP Function When the switch of this terminal acts the frequency setting
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......