HLP-A Series
HLP-A Series
-
54
-
Setting: CD066=50 CD067=0 CD068=0
CD069=0 CD070=0
Note: t his cu r ve is a k ind of special
application of reverse ramp setting. When
using transmitter for the control of pressure,
temperature and others and while the control
has higher pressure and output signals but
requiring the corresponding commands of stop
or deceleration on the inverter this curve can
satisfy the demand properly.
Setting: CD066=10 CD067=1 CD068=40
CD069=0 CD070=1
Note: this method is used extensively. The user
can use it flexibly.
Setting: CD066=10 CD067=1 CD068=40
CD069=0 CD070=1
Note; this curve is the extension of the above
curve. 2V~10V (4.8mA~20mA) corresponds to
0Hz~40HZ; the signal of 0V~2V(4~4.8mA)is
invalid. It can be used to avoid noice
disturbance. In harsh environment it is better
not to use signals below 1V for setting the
operating frequency of the inverter.
CD071 AM Analog Output Gain
Set Range: 0.0—100.0%
Unit: 1%
Factory Setting: 100.0
This parameter can be used to adjust the output voltage value of Multi-output
6 to adapt to f requency meters with different measuring range and also
used to correct a f requency meter. For example, for an externally connected
frequency meter with the measuring range of 0~5V, a multi-f unction terminal
can be used to display its operating frequency. Then it can be corrected with
this parameter. It can be achieved by setting CD071=50 .
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......