HLP-A Series
HLP-A Series
-
52
-
CD061 Uniform Frequency 1
**
CD062 Uniform Frequency 2
Set Range: 0.00—400.00 Hz Unit: 0.01 Hz Factory Setting: 0.00
CD063 Uniform Frequency Range
**
Set Range: 0.10—10.00 Hz Unit: 0.01 Hz Factory Setting: 0.50
When the output f requency is more than the uniform f requency the
corresponding multi-outputs will act. The uniform frequency range acts as a
hysteresis loop.
When the inverter is in the operation of multi-pumps, CD061 (Uniform
Frequency 1) is used as high speed f requency and CD062 is set as low speed
operating f requency. The def initions of the corresponding multi-f unction
contacts are changed.
When output F. is higher than uniform F, the corresp. multioutputs act.The
uniform F. range is uaed as hysteresis LOOP.
CD064 Counting Value
**
Set Range
:
0—65500
Unit: 1
Factory Setting: 0
An external terminal of multi-f unction can be used as a trigger for the
counter. When the counter reaches the set value of CD064 the corresponding
multi-output contact will act. After the counter is cleared and reset it will start
counting again. A proximity switch or optoelectronic switch can be used for
the triggering signals.
CD065 Analog Input
Set Range: 0—7
Unit: 1
Factory Setting: 0
0: 0~10V 1: 0~5V 2: 0~20mA
3: 4~20mA 4: 0-10V and 4-20mA stacked 5-7: Invalid
This parameter can be set for different analog input signals.
When CD065=4, the output frequency =1/2 (U/Umax + I/Imax )× 50Hz
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......