HLP-A Series
HLP-A Series
-
77
-
If DATA is one word, the LEN=3, If DATA is one byte, the LEN=2 .
When inverter has no this f unction code or reply no effect, the format as
follows :
ADDR 81H 01 FUNC
b : Write f unction code data
Format :
ADDR 02 LEN FUNC Data
ADDR=0 for broadcast, it write to all inverter, but no reply.
ADDR≠0, set data and reply from inverter of this address.
When the setting is incorrect or the inverter does not have this f unction, the
format returned is as follows:
ADDR 81H 01 FUNC
c: Control commands
Format:
ADDR 03 LEN CNTR
ADDR=0 for broadcast, it write to all inverter, but no reply
ADDR≠0, reply and return.
CNTR
7
6
5
4
3
2
1
0
jogr
jogf
jog
r/f
stop
rev
for
run
When the setting is correct it will return to present control status.
Format: ADDR 03 LEN CNST
CNST
7
6
5
4
3
2
1
0
Track start Braking
r/f
jogging running
r/f
jog
run
When the check is not correct,
ADDR 83H 01 CNST
d: Read status value
Format :
ADDR 04 01 CFG
ADDR=0, no reply
ADDR≠0, reply.
CFG=0~7, reply single data
0 : Set F 1 : Out F 2 : Out A 3 : RoTT
4 : DCV 5 : ACV 6 : Cont 7 : Tmp
For example: read agreed frequency
Send : 01 04 03 00 CRC
Return : 01 04 03 13 88 CRC
In which, 13 88 are data
13 for high order, while 88 for low order.
(4) LEN : data length, It means the length of D(n-1)…D0, Length set: when one
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......