HLP-A Series
HLP-A Series
-
32
-
Parameter and Function List (Part 5)
Category
Code
Function
Set Range & Function
Explanation
Factory
Setting
CD095
AutoPLC Memory
0~1
0
CD096
~
CD109
Reserved
Mu
lti-
spe
ed
a
nd
E
asy
PL
C
CD110 Number of Auxiliary
Pump
0~2
0
CD111
Continuous
Operating Time of
Aux.Pumps
1~9000min
60
CD112 Interlocking Time of
Aux.Pumps
0.1~250S
*
CD113 High Speed Running
Time
1~250S
60
CD114 Low Speed Running
Time
1~250S
60
CD115 Stopping Voltage
Level
1~150%
95
CD116
Lasting Time of
Stopping Voltage
Level
1~250S
30
CD117
Wakeup Level
1~150%
80
CD118
Sleep Frequency
0.00~400.00Hz
20.00
CD119
Lasting Time of Sleep
Frequency
1~250S
20
Pa
ram
et
ers
of
P
rot
ect
ion
F
un
ctio
ns
CD120 Over-voltage Stall
Prevention
0: Invalid 1: Valid
1
CD121 Stall Prevention Level
at Accel.
0~200%
150
CD122 Stall Prevention Level
at Constant Speed
0~200%
0
CD123 Stall Prevention Level
at Decel.
0~232%
0
CD124
Over-torque Detect
Mode
0~3
0
CD125
Over-torque Detect
Level
0~200%
0
CD126
Over-torque Detect
Time
0.1~20.0S
1.0
CD127
Decel. time for stall
prevention at constant
speed
5.0
CD128 Fault restart time
1.0
CD129
Voltage rise time
during frequency
track
5
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......