HLP-A Series
HLP-A Series
-
51
-
28: PID Lower Limit Alarm: This contact will act when the PID feedback is
smaller than the lower limit (the set value of CD156).
29: PID Upper Limit Alarm: This contact will act when the PID feedback is
greater than the upper limit (the set value of CD155).
30: Fan act: When the temperature of the inverter is increased or it is in
running, this contact will act.
31: Electromagnetic Relay Act: When the contact pulls in, the corresponding
multi-f unction terminal will act.
32: Braking Resistor Act: When the inverter is in running and the DC voltage
reaches the braking voltage the contact will act.
CD060 Multi-Output AM
**
Set Range: 0—7 Unit: 1
Factory Setting: 0
Functions: Output terminal of digital f requency, generating pulse or 0—10V
analog. In combination with CD071 it can be connected with a corresponding
instrument with the measuring range below 10 to be used for external
monitoring.
0 : 0~10V analog output, corresponding to output f requency. 0~10V
corresponds to 0~Maximum operating frequency
1 : 0~10V analog output, corresponding to output current. 0~10V corresponds
to 0~two times of the rated current of the inverter.
2 : Analog output, corresponding to DC bus voltage. 0~10V corresponds to
0~1000V.
3 : Analog output, corresponding to AC output voltage. 0~10V corresponds to
0~510V/255V.
(Note: The machine type of three phase, 380V corresponds to 510V and the
machine type of single phase, 220V corresponds to 255V)
4 : Pulse Output, corresponding to operating f requency: 1 Pulse/Hz, (50% of
capacity ratio )
5 : Pulse Output, corresponding to operating frequency: 2 Pulse /Hz, (50% of
capacity ratio )
6 : Pulse Output, corresponding to operating frequency: 3 Pulse /Hz, (50% of
capacity ratio )
7 : Pulse Output, corresponding to operating frequency: 6 Pulse /Hz, (50% of
capacity ratio )
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......