HLP-A Series
HLP-A Series
-
44
-
CD044 Skip Frequency 1
**
CD045 Skip Frequency 2
CD046 Skip Frequency 3
Set Range: 0.00—400.00 Hz Unit: 0.01Hz Factory Setting: 0.00
CD047 Skip Frequency Range
**
Set Range: 0.10—10.00 Hz Unit: 0.01Hz Factory Setting: 0.50
These three f requency skipping points are set for avoiding a mechanical
resonance point. In case of CD047=0.1 , all skip f requencies are invalid. The
actual skip frequency range is two times that of CD047, as shown in the above
diagram.
CD048 Timer 1 Time
Set Range: 0.1~10.0S Unit: 0.1S Factory Setting: 0.1
CD049 Timer 2 Time
Set Range: 1~100S Unit: 1S Factory Setting: 1
Timer 1 is a timer of 0.1s ~ 10.0s and Timer 2 is a timer of 1s ~ 100s. When the
timer start at multi-inputs is closed (on) the timer starts to count time. When it
reaches the set time the corresponding multi-output contact will act. When the
timer start is opened (off ) the timer time at the multi-output will be reset.
For example, set CD048=5.0s. When the external control terminal (Multi-Input)
is valid the output terminal will be valid after five (5.0) seconds, the signal of
which can be used to control other corresponding signals.