HLP-A Series
HLP-A Series
-
57
-
multi-f unction terminals.
⑥
This main f requency can be set in two ways. One method is to set it
through CD000 and another is to set it through the potentiometer.
When CD034 is set to 1 the f requency of Main Frequency is set by the
potentiometer. For the related parameters refer to CD000,CD034 and
CD080~CD086.
Note:
①
The frequency at each inflection point is determined by CD000 and CD080.
②
Skip Frequency is determined by CD086.
③
Running Time is determined by Timer CD087 and CD088.
④
The related parameters: CD000, CD080~CD088.
4: Internal control Multi-speeds
Note:
①
Main speed and 7-speeds composes 8-speeds.
②
The ramp time of each speed step is set by PLC Ramp Time CD079. Refer
to the detail descriptions of CD079.
③
Running Time is set by Timer CD087~CD094. For the control steps not to
3: Disturbance (Traverse f unction)
This is a special parameter in the chemical f iber and printing and dying
industries to realize the traverse f unction. Except the commands of stop,
external faults and emergency stop all other commands are not accepted at
running.