HLP-A Series
HLP-A Series
-
99
-
(2) Parameter CD033=1, FOR terminal controls operation
CD055=31 SPL terminal is set for Auto PLC reset suspend f unction.
CD095=1
Auto PLC Memory CD077=1 Cycling run
CD076=4 Internal control multi-speed
CD080=15 CD084=20 CD082=25 CD000=10
CD087=10 CD088=10 CD089=10 CD090=10
(3) Operating curve
(4) Operation description
①
(K1) FOR is closed and the inverter will run according to the program set by
internal control multi-speeds.
②
When it is required to stop due to fault and process or other reasons, K1 will
be opened. And the inverter will stop output and suspend counting time. After
the fault is removed K1 will be closed and the inverter will continue to run
according to original program.
③
When it is required to run again f rom the beginning due to fault and
process stop K1 should be opened. Press K2 to reset. By closing K1 it will restart
to run.
example the switching is made through the panel)
9. Example application of Auto PLC Suspend
Requirement: Auto PLC can be suspended during the internal control multi-
speed run. After handling the related problems it can resume.
(1) Connection