HLP-A Series
HLP-A Series
-
21
-
Model
NFB(A) Input wire
mm
2
Output wire
mm
2
Control
wire
mm
2
Screw
HLPA022043B
800
150×2
150×2
1
M16
HLPA025043B
800
150×2
150×2
1
M16
HLPA028043B
800
150×2
150×2
1
M16
HLPA030043B
800
150×2
150×2
1
M16
HLPA031543B
1000
185×2
150×2
1
M16
HLPA034543B
1000
185×2
150×2
1
M16
HLPA037543B
1200
240×2
185×2
1
M16
HLPA040043B
1200
240×2
185×2
1
M16
HLPA041543B
1200
240×2
185×2
1
M16
2) For control circuit wiring (signal line)
● The signal line should be separately laid in a different conduit with the
main circuit wire to avoid any possible interference.
● Please use the shielded cable with the size of 0.5-2mm2 for signal lines.
● Use the control terminals on the control panel correctly according to
your needs.
3) Grounding
● Grounding terminal E. Be sure to make correct grounding
220V class: The third grounding method (Grounding resistance should
be 100Ω or lower.)
380V class: The special third grounding method (Grounding resistance
should be 10Ω or lower.)
● Choose grounding wires according to the basic length and size of the
technical requirements of the electric equipment.
● Do avoid sharing grounding wire with other large power equipment
such as electric welder, power machine, etc. The grounding wire
should be kept away from the power supply wires for large power
equipment.
● The grounding method for several inverters together should be done as
the first and second diagrams below. Avoid the third loop.
● The grounding wire must be as shorter as possible.
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......