HLP-A Series
HLP-A Series
-
56
-
Multi-f unction Terminals
Results
Multi-speed
1
Multi-speed
2
Multi-speed
3
OFF
OFF
OFF
Main frequency and frequencies
are determined by CD000 or
potentiometer.
ON
OFF
OFF
Multi-speed 1 and frequency are
determined by CD080.
OFF
ON
OFF
Multi-speed 2 and frequency are
determined by CD081.
ON
ON
OFF
Multi-speed 3 and frequency are
determined by CD082.
OFF
OFF
ON
Multi-speed 4 and frequency are
determined by CD083.
ON
OFF
ON
Multi-speed 5 and frequency are
determined by CD084.
OFF
ON
ON
Multi-speed 6 and frequency are
determined by CD085.
ON
ON
ON
Multi-speed 7 and frequency are
determined by CD086.
Note:
①
It is only valid to realize the external control 8-Speeds operation when
Multi-inputs are set for Multi-speed 1, 2, 3 and CD076 is set to 2.
②
Multi-speed 1, 2, 3 can be used to make up 7-Speeds and 8-Speeds adding
the main frequency .
③
The frequencies of Speed Step 1 ~ Step 7 are determined by CD080~CD086.
④
Each ramp time is determined by the external multi-f unction terminal.
⑤
The directions of each program operation are determined by the external
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......