CD113 and CD114 must be used in combination of CD061, CD062 and multi-
outputs. Their main f unction is to increase or decrease the number of auxiliary
pump.
This parameter is set for the voltage level of the master pump entering into
sleep mode. For details refer to the following description.
*CD115 Stopping Voltage Level
Set Range:0~150%
Unit:1%
Factory Setting:95
This parameter is set for the lasting time under the stopping voltage level
before entering into sleep mode. For details refer to the following description.
*CD116 Lasting Time of Stopping Voltage Level
Set Range:1~250S
Unit:1S
Factory Setting:30
This parameter is set for the wakeup voltage level from sleep to wakeup.
*CD117 Wakeup Voltage Level
Set Range:1~150%
Unit:1%
Factory Setting:80
This parameter is set for the lowest operating f requency entering into sleep
mode.
*CD118 Sleep Frequency
Set Range: 0.00~400.00Hz Unit: 0.01Hz Factory Setting:20.00
This parameter is set for the lasting time to run at sleep f requency when
entering into sleep mode.
*CD119 Lasting Time of Sleep Frequency
Set Range: 1~250S Unit: 1S Factory Setting:20