HLP-A Series
HLP-A Series
-
106
-
Appendix 4: Description of Parameter Setting for HLP-A
Inverter
1. Requirements:
Use a potentiometer to control the speed and a button to control starting or
stopping of the inverter.
2. Setting requirements:
1) Wiring
⑴
220V power supply, connecting to any two terminals of R, S, T, 3φ220
connecting to R, S, T terminals; 3φ380 connecting to R, S, T terminals, paying
attention to the machine model. Do not mistake the inverter s of 380V class and
220V class.
Special attention:
Connecting of the inverter of 220V class to 380 V class power will cause
blowup of the inverter. The earth wire need to be connected separately to earth
and must not be connected to zero line.
⑵
U
、
V
、
W should be connected to the motor and the earth wire must be
correctly (separately) connected to earth.
⑶
The three ends of potentiometer are respectively connected to +10V,
VI, ACM. Adjust the speed. VI terminal is connected to the center tap of
potentiometer.
⑷
External switches are connected to the terminals of FOR, DCM ( Control
operation ) .
2) Wiring Diagram
Single phase 220V inverter as
example
3) Parameter Setting
⑴
Turn on the power to display the version number, later 000.00 ;
⑵
Press Key “PROG”
(
Program
)
to enter to enter to programming status
showing CD000;
⑶
Modify the parameter of CD033 to set the operation mode for the operation
with external terminal. Press Δ to reach CD033 or use ←, Δ to make the
display reach CD033 (Note: Key ← is for shifting), and then press Key “SET”
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......