HLP-A Series
HLP-A Series
-
38
-
CD011 Parameter Reset
Set Range: 00-10
Unit: 1 Factory Setting: 00
When the value for a parameter is set improper or is abnormal for some
reasons this parameter can be set to 08 to restore it to the factory setting and
then reset. After the parameters are locked (in case of CD010=1) the parameters
can’t be reset. They can only be reset after unlock. For related parameters refer
to CD010.
CD012 Accel. Time 1
**
Set Range: 0.1—6500.0S
Unit: 0.1S
Factory Setting: *
CD013 Decel. Time 1
**
Set Range: 0.1—6500.0S
Unit: 0.1S Factory Setting: *
CD014 Accel. Time 2
**
Set Range: 0.1—6500.0S
Unit: 0.1S Factory Setting: *
CD015 Decel. Time 2
**
Set Range: 0.1—6500.0S
Unit: 0.1S
Factory Setting: *
CD016 Accel. Time 3
**
Set Range: 0.1—6500.0S
Unit: 0.1S
Factory Setting: *
CD017 Decel. Time 3
**
Set Range: 0.1—6500.0S
Unit: 0.1S
Factory Setting: *
CD018 Accel. Time 4
**
Set Range: 0.1—6500.0S
Unit: 0.1S
Factory Setting: *
CD019 Decel. Time 4
**
Set Range: 0.1—6500.0S
Unit: 0.1S
Factory Setting: *
Ramp-up time means the time needed for the inverter to increase the
f requency f rom 0Hz to the maximum operating f requency (See t1 in the
This is set for preventing workers f rom false operation to avoid over-heat or
some other mechanical faults, which might be caused due to too low operating
frequency.
The setting of Frequency Lower Limit must be less than the set value of
CD007.
CD010 Parameter Lock
**
Set Range: 0-1 Unit: 1
Factory Setting: 0
0: Invalid.
1: Valid, i.e. the parameters are locked. Except this parameter other parameters
can not be changed.
This parameter is set to prevent non-maintenance personnel f rom setting
other parameters by mistake. After the parameters are locked the operating
frequency can be changed by pressing
or .
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......