HLP-A Series
HLP-A Series
-
16
-
Symbol
Function Description
Factory setting
EV
+12V Power Supply
M a x . o u t p u t c u r r e n t
200mA
P24
+12V Power Supply
M a x . o u t p u t c u r r e n t
200mA
+10
Power Supply for Speed S10V/20mA
VI
A n a log Volt a ge Fr e q u e n c y
Reference Input
0 ~+10V cor responding
to the highest operating
frequency
AI
A n a log C u r r e nt Fr e q ue nc y
Reference Input
4~20mA corresponding
to the highest operating
frequency
AO
Output current
VO
Output voltage
ACM Common Terminal of Analog and
Control Signals
DRV Multi-Output 1
(Optical couple output)
DC12V/100mA
UPF
Multi-Output 2
(Optical couple output)
FA
FB
FC
Multi-Output 3 (N/O or N/C)
3A/250VAC, 3A/30VDC
KA
KB
Multi-Output 4 (N/O)
3A/250VAC, 3A/30VDC
AM
Output terminals of digital
frequency
0~10V
RS+ RS- RS485 Communication port
3. Basic Connection Diagram
The wiring of the inverter is divided into two parts, main circuit terminal
connections and control circuit terminal connections. The user can
see the main circuit terminals, and the control circuit terminals after
removing the cover of enclosure. The terminals must be connected
correctly as the following wiring circuit diagrams.
The following diagram shows the factory standard connection of Model
HLP-A
Summary of Contents for HLP-A Series
Page 1: ......
Page 2: ...HLP A Series...
Page 3: ......
Page 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Page 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Page 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Page 117: ......