GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-23
Table 7-5: Emergency Services
Field Variable
Min
Max
Initial Units
EMS/HSafterCB
0
1
0
-
EMS (Emergency Medical Service)/HS(Hospital
Service) after Code Blue.
This is a Code Blue bypass
control.
0 = Car goes from Auto to Hospital service,
bypassing the code blue sequence, when EMS
switch is turned on.
1 = Hospital service only activates after a code blue
recall.
F1 DC Tim-out
10
60
20
sec
Fire Phase 1 Door Close Time-out.
The amount of
time it will take before the car doors start to close
while the car is on Independent or Attendant
service prior to recalling the elevator on Fire Phase
1.
F1 Door Dwell
1
90
60
sec
Fire Phase 1 Door Dwell time.
Fire Service Phase
one complete dwell time when 'Cl Door F1 Rcl'
parameter is set. (Denver FS phase1 dwell time)
F2 STP Recovr
0
1
0
-
Fire Service Phase 2 Recovery.
After special device
that prevents the car from running up has been
activated. These devices are the Low Oil Switch,
Hot Oil Switch, and battery backup lowering.
Hydro Only
F2DOB ovr DCB
0
1
0
-
Fire Phase 2 Door Open Button Overrides the
Door Close Button.
1 = Allows Door Open Button will override Door
Close Button on phase 2.
Fire Main Flr
Bottom
Floor
Top
Floor
1
floor
Fire Main Floor
Fire Option
0
3
0
-
Fire Option.
Recall Reset Selection:
0 = Reset fire service phase 1 after hall switch is
turned off and car returns to fire floor.
1 = Reset phase 1 immediately after hall switch is
turned off.