GALaxy eHydro Elevator Controller Section 6
– Main CPU Faults & Detailed Faults
6-55
Table 6-0: Main CPU Faults
Faults
Description
Possible Cause/Suggested Fix
EP Recall Car 7 OTS
Emergency Power
Recall Car Out of
Service Car 7. Car 7
was out of service
while elevators were
in
an Emergency Power
Recall Sequence.
• Check faults for car 7
EP Recall Car 8 OTS
Emergency Power
Recall Car Out of
Service Car 8. Car 8
was out of service
while elevators were
in an Emergency
Power Recall
Sequence.
• Check faults for car 8
EPRecall Car1 Tim-ot
Emergency Power
Recall Time-out Car 1.
Car 1 timeout while it
was in Emergency
power recall mode.
• Make su
re the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
•
Verify the speed of the car during recovery operation.
EPRecall Car2 Tim-ot
Emergency Power
Recall Time-out Car 2.
Car 2 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify t
he speed of the car during recovery operation.
EPRecall Car3 Tim-ot
Emergency Power
Recall Time-out Car 3.
Car 3 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
EPRecall Car4 Tim-ot
Emergency Power
Recall Time-out Car 4.
Car 4 timeout while it
was in Emergency
power recall mode.
•
Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.