GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-36
Table 7-7: Group Options
Field Variable
Min
Max
Initial Units Description
GrpCC Sec OvT
1
240
60
Sec
Group Car Call Security Override Timer.
This is the
amount of time that the car call security is overridden
when a group car call security override button is
pressed.
Handicap Wait
0
255
0
Sec
Handicap Car Wait Time.
Special operation that
when a passenger presses a handicap hall button, the
group adds this time to the ETA of all cars that do not
have enough capacity. See Handicap Capacity in car
options. Normally, if a car is at the floor of the
handicap hall call, it will get the assignment
regardless of the handicap capacity unless this value
is set to 255.
HC Secur ctrl
0
2
0
-
Hall Call Security Control.
Set what riser the hall call
security inputs work with:
0 = Only standard hall calls
1 = Standard hall calls and Second Riser hall calls
2 = Only Second Riser hall calls
HC X-AssignEn
0
5
0
-
Hall Call Cross Assignment Enable.
1 = Front
Hall Call Cross Assignment
is enabled.
4 = Rear
Hall Call Cross Assignment
is enabled.
5 = Front and rear H
all Call Cross Assignment
is
enabled. The group will look for cross assignment
calls as well as hall calls.
Power should be cycled on controller after this
variable is modified so all communications to all
devices are made.
2 =
Hall Call Cross Cancellation
is used and hall calls
are are not cancelled when all cars are out of service.
A setting of 3 for both hall call assignment and
cancellation
is not valid
and may cause unpredictable
results.