GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-35
Table 7-7: Group Options
Field Variable
Min
Max
Initial Units Description
EP ATTcar 1st
0
1
0
-
Emergency Power Attendant Car First.
Select and
Prioritize the attendant car for running on emergency
power service. It won't be recalled. After recall is
complete for the group, It recovers and goes back in
service
EP Man Sel En
0
3
1
-
Emergency Power Manual Select Enable.
0 = The recall sequence is aborted and any moving
car will stop at the next floor to allow the selected car
to run.
+1 = Car is selected to run when the currently
selected car completes its recall.
+2 = Makes the selected car wait for all the cars to
recall before being selected to run.
EP Rcl Out En
0
1
0
-
Emergency cars finished Recalling Output Enable.
It enables an output in the hall call board for
Emergency Power Complete (EPCOM). This setting is
only read in power up so after changing this setting
you need to reboot the controller.
EP Recall Dly
0
3200
30
Sec
Emergency Power Recall Delay Time.
Time delay
before the group starts the emergency power recall
sequence.
EP Recovr Tim
1
60
20
Sec
Emergency Power Recover Time.
When elevators
are in Emergency Power recall, this is the time that
the dispatcher will wait for each car to recover to a
floor. If the car is in the middle of a blind shaft, you
need to calculate the time each car may take to get
to a floor in emergency power recovery speed.
GrpCC Ovrride
0
1
0
-
Group Car Call Override.
Normally visitor access
allows the car call security to be overridden
momentarily from a push button in an owners
apartment. With this parameter set to 1, the security
override works directly from a key switch input.