GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-26
Table 7-5: Emergency Services
Field Variable
Min
Max
Initial Units
Rcl frm F1Alt
0
1
0
-
Recall From Fire Phase 1 Alternate floor.
If the car
has returned to the alternate floor from a smoke
sensor and when two fire hall switch are used, both
must be on to recall the car from the alternate floor
to the main floor.
1 = The car will recall from the alternate floor to the
main floor from either hall fire key switch.
(set to 1 for Mass. fire service.)
Recall Reset
0
3
0
-
Recall Reset Selection.
0 = Reset fire service phase 1 after hall switch cycled
through reset and turned off and car returns to fire
floor.
1 = Reset phase 1 immediately after hall switch is
cycled through reset and then turned off.
2 = Reset fire service without cycling fire switch
through reset but turned off only if the smoke
sensors were not activated.
Recall Reset2
0
1
0
-
Recall Reset Selection 2:
0 = Reset fire service phase 1 with car at any floor.
1 = Reset phase 1 only if car at fire recall floor.
Table 7-6: Group Dispatch
Field Variable
Min
Max
Initial
Alt Lbby Flr
1
Top
Floor
1
Alternate Lobby Floor.
Galaxy groups can be
configured to have an alternate lobby. Switching
between regular lobby and alternate lobby can be
done by means of liftnet, Galileo, controller input or
service timer. Once the alternate lobby is enabled,
controllers will use this landing as the lobby floor for
all dispatching purposes.
Alt Parkin Fl
1
Top
Floor
1
Alternate Parking Floor.
Normally, during parking
operation, one elevator is always parked at the lobby.
With alternate parking floor operation, a free car is
parked at the alternate parking floor instead of the
lobby floor. This operation is controlled by an input
or from a service timer.