GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-7
Table 7-2: Car Timers
Field Variable
Min
Max
Initial Units Description
OSER SSopen T
0
900
60
sec
Out of Service Safety String Open Time.
Time to
control the OSERL output. Used with OSERL control
option 1 for ' SS open' set to 4.
Pas Chime Tim
0.2
2
0.5
sec
Floor Passing Chime Time.
Length of time the floor
passing chime will sound when a floor is passed.
RC Pick Delay
0
7
0
sec
Retiring Cam Pick Delay.
The amount of delay time
for the retiring cam to pick once the doors are closed.
RCDrop Fail T
0.5
5.5
0.5
sec
Retiring Cam Drop Fail Time.
Retiring cam drop fail
safe delay for manual doors. Delay time when car
arrives to the floor before it drops the output.
Relev Dly Tim
0
2
1
sec
Relevel Delay Time.
The amount of delay time before
the car will re-level. This would be used for jobs that
have excessive rope stretch.
Reset Time
0
10
5
sec
Reset Time.
Delay time in the reset mode before
allowing the car to run.
RTL Dwell Tim
1
60
8
sec
Return To Lobby Dwell Time.
If Return To Lobby is
set to cycle doors at the lobby, use this timer to
control how long they will dwell before closing in
return to lobby mode.
Run Cycle Tim
0
300
0
hours
Run Cycle Time.
Used to initiate a run when the
elevator has been sitting idle for a period of time.
Used for jobs that have high friction bearing
machines.
Sabb Buzz Dly
1
10
5
sec
Sabbath Door Buzzer Timer
(prior to doors closing).
Jobs where the light curtain is disabled in Sabbath
operation require a buzzer prior to the door closing
sequence. This timer warns people the light curtains
are about to be enabled (output name: SABUZ)