GALaxy eHydro Elevator Controller Section 6
– Main CPU Faults & Detailed Faults
6-95
Table 6-2: Faults from the Hall Call Driver Board Devices on the GRCAN Serial Port
Fault
Description
Possible Cause/Suggested Fix
Up LED Open
HCB led open up
• Make Sure there is a
GALX-1056AN attached to the proper
connector (Up LED always attached to CN5, Down LED attached to
CN5 if only down call at that station (like the top floor), otherwise
attached via ribbon at CN6.
• Replace GALX
-1056AN for the associated up or down call.
Up LED Short
HCB led short up
• Make Sure there is a GALX
-1056AN attached to the proper
connector (Up LED always attached to CN5, Down LED attached to
CN5 if only down call at that station (like the top floor), otherwise
attached via ribbon at CN6.
• Repla
ce GALX-1056AN for the associated up or down call.
Up LED Short
HCB led short up
• Make Sure there is a GALX
-1056AN attached to the proper
connector (Up LED always attached to CN5, Down LED attached to
CN5 if only down call at that station (like the top floor), otherwise
attached via ribbon at CN6.
• Replace GALX
-1056AN for the associated up or down call.