GALaxy eHydro Elevator Controller Section 6
– Main CPU Faults & Detailed Faults
6-71
Table 6-0: Main CPU Faults
Faults
Description
Possible Cause/Suggested Fix
NTS UNFailed Off
NTS UN I/O Failed Off
during start or
leveling. The
controller is
attempting to run the
car in the up direction
but the UN input is
off.
• The UN output failed.
Replace the UN output module.
•
The UN input failed. Replace the UN input board.
• The NTS
processor has turned the UN output off. Check for errors
from the NTS processor.
• The NTS processor has a position
error from the APS selector. Verify the setup of the APS
selector and that the NTS processor is communicating with
the selector.
• The Safety PAL has determined that it is
unsafe to run the car such as the doors are open. Check for
a Safety Pal Fault and checkthe status of the I/Os of the
Safety PAL.
NTS UN
Failed On
NTS UN I/O Failed On
during start. As part of
the redundancy check,
the Main CPU sends a
command to the NTS
processor to turn of
the UN, DN, UT and
DT outputs prior to
turning on any valve
outputs to verify that
the NTS outputs have
not faulted on. During
this process, the UN
output or the UN
input stayed on.
• UN output shorted on. Replace the output module.
• UN input failed on. Replace the input board.
• UN test jumper left on the module. Remove the test
jumper.
NTS UT
Failed Off
NTS UT I/O Failed Off
during start. The
controller is
attempting to run the
car high speed in the
up direction but the
UT input is off.
• The UT output failed. Replace the UT output module.
• The NTS processor has turned the UT output off. Ch
eck
for errors from the NTS processor.
• The NTS processor has a position error from the APS
selector. Verify the setup of the APS selector and that the
NTS processor is communicating with the selector.
• The Safety PAL has determined that it is unsafe to
run the
car such as the doors are open. Check for a Safety Pal Fault
and check
the status of the I/Os of the Safety PAL.