GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-8
Table 7-2: Car Timers
Field Variable
Min
Max
Initial Units Description
Sabbath Dwell
1
60
10
sec
Sabbath Door Dwell Time.
Car will wait this amount
of time on every floor for Sabbath operation except at
the lobby where it will follow the handicap dwell door
time (separate timer).
Sec Dis Time
0
3200
0
sec
Security Disable Time.
This timer is used with a
security disable input button at the lobby. When the
button is pressed, the car call security is disabled for
the time value set from this parameter.
Shrt Dwll Tim
0
60
1
sec
Short Door Dwell Time.
Door open dwell time when
the doors re-open on a door open button, electric
eye, safety edge or door hold button.
Shutdn Alrm T
5
1500
120
sec
Shutdown Alarm Timer.
Stall Time
20
3200
60
sec
Stall Time.
Maximum time a run is requested but the
car is not moving.
VIP Door Time
1
3200
20
sec
VIP Door Time.
The amount of time the car will park
at the VIP recall floor prior to going to automatic
service.
Y Delta Time
1
5
1.5
sec
Y-Delta Time.
Transfer time to change motor from Y
start to Delta run. Timer also used for DEL or MCX
turn on time with controllers without y-delta starters.
Table 7-3: Car Options
Field Variable
Min
Max
Initial Units
2nd Risr Lant
0
1
0
-
Second Riser Lantern.
Turn on cab lantern only when
IR call answered. If this parameter is set cab lanterns
will only turn on when answering second riser calls.