GALaxy eHydro Elevator Controller Section 6
– Main CPU Faults & Detailed Faults
6-98
Table 6-3: Faults from the COP Board Devices on the CTCAN Serial Port
Fault
Description
Possible Cause/Suggested Fix
No LED Board
Car Call LED board missing
• Faulty LED signal from RGB Board. Look at detailed
car faults log to determine device. 'dev' gives you
address for global CAN device, 'dv2' gives you local
CAN device and 'pf1' the number for the IO location
within the local board.
Stuck Button
Car Call Board stuck button
• Faulty LED signal from RGB Board. Look at detailed
car faults log to determine device. 'dev' gives you
address for global CAN device, 'dv2' gives you local
CAN device and 'pf1' the number for the IO location
within the local board.