GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-44
Table 7-8: Color Lights
Field Variable
Min
Max
Initial
Emer Lt Color
0
15
0
Emergency Light Color.
0 Based on Parameters1 Red2
Orange 3 Yellow4 Chartreuse 5 Green6 Aquamarine 7
Cyan8 Azure 9 Blue 10 Violet11 Magenta 12 Rose13
Rose White 14 Warm White 15 Cool White
Fir Lt Bright
0
100
100
Fire Light Brightness
Fire Lt Color
0
15
0
Fire Light Color.
0 Based on Parameters
1 Red
2 Orange
3 Yellow
4 Chartreuse
5 Green
6 Aquamarine
7 Cyan
8 Azure
9 Blue
10 Violet
11 Magenta
12 Rose
13 Rose White
14 Warm White
15 Cool White
HC Off Bright
0
100
20
Hall Call Off Brightness.
Select the brightness for LED
hall call button, when button is NOT pressed. Used
only with GAL serial hall button fixtures.