GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-6
Table 7-2: Car Timers
Field Variable
Min
Max
Initial Units Description
Lobby Dwell
1
60
5
sec
Lobby Dwell.
Door open dwell time for a car at the
lobby.
Lt/Fan Time
30
3200
360
sec
Generator Run/Cab Light/Fan Time.
Length of time
to leave the generator running or the Cab light and
fan on after there is no longer a demand to run.
ManDo Buz Dly
0
900
0
sec
Manual Door Buzzer Delay.
On a car with manual
doors, sound the buzzer if the door is left open and a
call is entered after this time delay. This function is
disabled when set to zero.
Mx Door Hld T
0
3200
0
sec
Maximum Door Hold Time.
Maximum time to be
allowed when the extended dwelling input (ED) is
pressed. If set to zero, there will be no limit on how
long the car will be held on ED. When set to a value,
this will be the maximum allowed time for the car to
be held by ED input, then car will go on regular
dwelling timers (car or hall call dwelling timers)
NonInterfer T
1
60
2
sec
Non-Interference Time.
Time between when you stop
and when you can run again.
Nudging Time
20
3200
60
sec
Nudging Time.
Delay time for a door to be held
before going into nudging.
OSER BtwFlr T
0
900
60
sec
Out of Service Between Floors Time.
Timer to
control the OSERL output. Used with OSERL Control
option 1 for 'between floors for over a minute' set to
2.
OSER NoCall T
0
900
600
sec
Out of Service Not Responding to Calls Time.
Timer
to control the OSERL output. Used with OSERL Control
option 1 for 'not responding to calls' set to 1.