GALaxy eHydro Elevator Controller Section 6
– Main CPU Faults & Detailed Faults
6-56
Table 6-0: Main CPU Faults
Faults
Description
Possible Cause/Suggested Fix
EPRecall Car5 Tim-ot
Emergency Power
Recall Time-out Car 5.
Car 5 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
EPRecall Car6 Tim-ot
Emergency Power
Recall Time-out Car 6.
Car 6 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
EPRecall Car7 Tim-ot
Emergency Power
Recall Time-out Car 7.
Car 7 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
EPRecall Car8 Tim-ot
Emergency Power
Recall Time-out Car 8.
Car 8 timeout while it
was in Emergency
power recall mode.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
•
Verify the speed of the car during recovery operation.
Estop Fault
An emergency stop
occurred while moving
or attempting to
move. This fault is
recorded after three
emergency stops
occurred in a row.
• Lost UN while running up at
contract speed.
• Lost DN while running down at contract speed.
• The MC contactor did not energize or dropped out while
running
• The MC input did not turn on or dropped out while
running.
• The stop switch was pulled while running.
• The car was not safe
usually from clipping a door lock. See
Car Safe Fault.
• Low Pressure Switch activated during the run.
• Low Oil Switch activated during the run.
• High Temperature sensor activated during the run.
• The stall protection timer timed
-out.
• An emergency po
wer recall was initiated while the car was
running up.
FDoor Close Cont Flt
Door Close Contact
safe fault
• The car was either running or preparing to run and lost a
front door close contact input. Check the adjustment of the
door.