GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-28
Table 7-6: Group Dispatch
Field Variable
Min
Max
Initial
DnPk Trig Cnt
1
100
12
Down Peak Trigger Count.
Number of down hall calls
above the lobby that are set within the down peak
trigger time to place the system on down peak
operation.
DnPk Trig Tim
0
3200
60
Down Peak Trigger Time.
The time interval to count
the number of down hall calls above the lobby to
activate down peak operation.
DownPeak
Pool
0
Number
Cars
0
Down Peak Pool.
Number of cars to be utilized for
down peak.
DownPeak
Time
0
3200
180
Down Peak Duration Time.
The duration time for
down peak operation once down peak is activated.
ETA Co CC Tim
0
60
15
E
TA Coincident Car Call Time.
Hall calls will be
assigned to the car with the coincident car call unless
the car without the coincident car call can reach the
call faster then ETA Coincident Car Call Time.
ETA Min Time
0
60
6
ETA Minimum Time.
Minimum time for a hall call to
be assigned to a new car, the difference in ETA must
be greater than the ETA Minimum Time.
Grp TimerPark
0
Number
Cars
0
Group Service Timer Park Cars.
This is the number of
parking cars when parking is set from the Service
Activation Timer for Group parking.
Lobby Floor
Bottom
Floor
Top
Floor
1
Lobby Floor.
Lobby Req Ctl
0
1
0
Lobby Request Control.
If the lobby request variable
is set to non-zero, then that is how many cars are
requested to the lobby all the time. When this flag is
set to 1, the lobby request is only used when next up
is active. Next Up can be active all the time, from a
dedicated input or from Up Peak.