GALaxy eHydro Elevator Controller Section 7
– Main CPU Adjustable Variables
7-5
Table 7-2: Car Timers
Field Variable
Min
Max
Initial Units Description
Hall Lant Dly
0
15
0
sec
Hall Lantern Delay Time.
By default, when set to
zero, hall lanterns go off as soon as the car starts to
slow down to arrive at a floor. When set to a nonzero
value, this will be used as a timer for the hall lantern
to go off prior to arriving at the floor. For example, if
set to three seconds, hall lanterns will turn on
approximately three seconds before the car arrives to
the floor regardless of the speed of the car. We
recommend to set this parameter for high speed cars.
Handicap Dwll
1
120
25
sec
Handicap Dwell.
Extended door time from pressing
the ED button in the car.
HC Dwell
1
60
4
sec
Hall Call Dwell.
Door open dwell time when
answering a hall call or both a hall and car call.
HEOF AutoRstT
0
3200
0
sec
HEOF Auto Reset Time.
When the hall elevator off
function is activated from the HEOF input being
turned on, the car will be taken out of service until
the input is turned off. Once the input is off, the car
will stay out of service until the auto reset timer times
out.
IND Rcl2Lby T
10
60
20
sec
Independent Recall to Lobby Timer.
Recall delay for
car in Independent when 'IND Rcl to Lby ' is set.
Lant Off Time
0
2
0.2
sec
Lantern Off Time.
Used for double stroke gongs. The
lantern off time is the delay time after the lantern
first turns on until it turns off.
Lant On Time
0
2
0.7
sec
Lantern On Time.
Used for double stroke gongs. The
lantern will turn on, turn off and then turn on again.
The Lantern on time is the delay time from when the
lantern first turns on until it turns on the second time.