Table C-5: Measurement Transducer Block Parameters
(continued)
Index
Number
Parameter
Description
33
DISTANCE
Distance from the tank reference point (normally the
lower side of the flange) to the product surface
34
SIGNAL_STRENGTH
Amplitude of the echo from the product surface. A high
value indicates a good reflection by the surface
35
SIGNAL_STRENGTH_UNI
Signal strength unit
36
ANTENNA_TYPE
Antenna type on the device (see
)
37
TCL
Tank Connection Length. Electrical distance between
the transmitter's reference point and the microwave
unit. Only for user defined antennas.
38
PIPE_DIAMETER
Still-pipe inner diameter, see
39
HOLD_OFF_DIST
Hold Off Distance defines how close to the gauge’s
reference point a level measurement is accepted, see
40
ANTENNA_SIZE
Still-pipe Array antenna size
41
OFFSET_DIST_G
Gauge Reference Distance (G), see
the Distance Offset (G) if a reference point other than
the lower side of the device flange is required.
42
TANK_HEIGHT_R
Tank Reference Height (R) is defined as the distance
between the upper reference point and the lower
reference point (zero level). See
.
43
BOTTOM_OFFSET_DIST_C
Minimum Level Offset (C) defines a lower null zone
which extends the measurement range beyond the
Zero Level Reference Point down to the tank bottom.
See
.
44
CALIBRATION_DIST
Calibration Distance is by default set to zero. It is used
to adjust the level measurement so that measured
levels match hand dipped levels. See
45
TANK_SHAPE
the 5900C for various tank geometries.
46
TANK_BOTTOM_TYPE
Tank Bottom Type. Optimizes the Rosemount 5900C
for measurements close to the tank bottom. See
.
47
TANK_ENVIRONMENT
. Mark the check
boxes that correspond to the conditions in your tank.
For best performance you should not choose more
than two options. See
.
48
TANK_PRESENTATION
.
49
PRODUCT_DC
Product dielectric constant
50
ENV_WRITE_PROTECT
Write protect
51
RM_VERSION_NUMBER
RM card version number
52
DEVICE_MODEL
Device Model
Reference Manual
F
OUNDATION
™
Fieldbus Block Information
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
305
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...