ALARM_TYPE
Allows one or more of the process alarm conditions detected by the AI
function block to be used in setting its OUT_D parameter.
OUT_D
Discrete output of the AI function block based on the detection of
process alarm condition(s). This parameter may be linked to other
function blocks that require a discrete input based on the detected alarm
condition.
VAR_SCAN
Time period in seconds over which the variability index (VAR_INDEX) is
computed.
VAR_INDEX
Process variability index measured as the integral of average absolute
error between PV and its mean value over the previous evaluation period.
This index is calculated as a percent of OUT span and is updated at the
end of the time period defined by VAR_SCAN.
4.11.10
Filtering
The filtering feature changes the response time of the device to smooth variations in
output readings caused by rapid changes in input. You can adjust the filter time constant
(in seconds) using the PV_FTIME parameter. Set the filter time constant to zero to disable
the filter feature.
Figure 4-17: Analog Input Function Block Timing Diagram
$
%
&
)
(
'
*
A. FIELD_VAL
B. PV_FTIME
C. 63% of Change
D. PV
E. OUT (mode in auto)
F. OUT (mode in man)
G. Time (seconds)
Reference Manual
Configuration
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
167
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...