4.12
Analog Output block
The Rosemount 5900C is supplied with two pre-configured Analog Output (AO) blocks
according to
. The block configuration can be changed if needed. See
CHANNEL
Select the channel that corresponds to the desired sensor measurement:
Table 4-9: AO Block Channels for the Rosemount 5900C
AO Block Parameter
TB Channel Value
Process Variable
Vapor Temperature
7
CHANNEL_VAPOR_TEMPERATURE
Pressure
8
CHANNEL_PRESSURE
User Defined
9
CHANNEL_USERDEFINED
Tank Temperature
10
CHANNEL_TANK_TEMPERATURE
Table 4-10: Factory Supplied AO Blocks for the Rosemount 5900C
AO Block
Channel
Units
1
CHANNEL_VAPOR_TEMPERAT
URE
deg C
2
CHANNEL_PRESSURE
bar
XD_SCALE
The XD_SCALE includes three parameters: 0%, 100%, and engineering units. Set the
XD_SCALE engineering unit to represent the unit for the AO block channel value.
Reference Manual
Configuration
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
169
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...