Table C-3: Definitions of Analog Input Function Block System Parameters
(continued)
Index Number Parameter
Units
Description
19
FIELD_VAL
Percent
The value and status from the transducer block or from the
simulated input when simulation is enabled.
20
UPDATE_EVT
None
This alert is generated by any change to the static data.
21
BLOCK_ALM
None
The block alarm is used for all configuration, hardware, connection
failure or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as the
Unreported status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active status, if
the subcode has changed.
22
ALARM_SUM
None
The summary alarm is used for all process alarms in the block. The
cause of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status parameter. As
soon as the Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing the Active
status, if the subcode has changed.
23
ACK_OPTION
None
Used to set auto acknowledgment of alarms.
24
ALARM_HYS
Percent
The amount the alarm value must return within the alarm limit
before the associated active alarm condition clears.
25
HI_HI_PRI
None
The priority of the HI HI alarm.
26
HI_HI_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI HI alarm
condition.
27
HI_PRI
None
The priority of the HI alarm.
28
HI_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI alarm
condition.
29
LO_PRI
None
The priority of the LO alarm.
30
LO_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the LO alarm
condition.
31
LO_LO_PRI
None
The priority of the LO LO alarm.
32
LO_LO_LIM
EU of
PV_SCALE
The setting for the alarm limit used to detect the LO LO alarm
condition.
33
HI_HI_ALM
None
The HI HI alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
34
HI_ALM
None
The HI alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
35
LO_ALM
None
The LO alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
36
LO_LO_ALM
None
The LO LO alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
37
OUT_D
None
Discrete output to indicate a selected alarm condition.
F
OUNDATION
™
Fieldbus Block Information
Reference Manual
September 2019
00809-0100-5901
300
Reference Manual
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...