5. Repeat for each device to be programmed. Use the
Remove
button if you wish to
change the list of devices to be programmed.
6. Click the
Browse
button to locate the flash program file. File extension *.cry is used
for these files.
7. Click the
Start Programming
button.
Now the
Start Device Programming
window appears.
8. Click the
Start Programming
button to activate device programming.
If a Rosemount 2460 System Hub is used, a maximum of 25 devices can be
programmed. If there are more devices the programming must be divided in two
steps.
9. Update the TankMaster installation by adding new *.ini files for the Rosemount
5900C gauge to the TankMaster installation folder:
Two *.ini files are used for the Rosemount 5900C, RLG.ini and RLG0xx.ini, where xx
is the identification code of the application software.
a) Copy the RLG.ini file to the
C:\Program Files\Rosemount\Server
folder.
b) Copy the RLG0xx.ini file to the
C:\Program Files\Rosemount\Shared
folder
.
Reference Manual
Service and troubleshooting
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
217
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...