2. Non-metallic surfaces and the surface of the painted housing may, under certain
extreme conditions, generate an ignition-capable level of electrostatic. Appropriate
measures must be taken to prevent electrostatic discharge.
3. Using the box provided on the nameplate, the User shall permanently mark the
type of protection chosen for the specific installation. Once the type of protection
has been marked it shall not be changed.
4. When installed as Ex ib Ga/Gb, the partition wall materials separating EPL Ga from
EPL Gb are constructed of different materials depending on the antenna option.
Please refer to Control Drawing D9240040-917 for the material type of each
antenna. The material shall not be subject to environmental conditions which might
adversely affect the partition wall.
5. Maximum Process Temperatures are as follows:
When option n=Tank Seal
O-ring Type
Min/Max Process
Temperature Range
PV or QV
Viton
-15°C to +180°C
PK, FK, HK or QK
Kalrez
-20°C to +230°C
PE or QE
EPDM
-40°C to +110°C
PB or QB
BUNA-N
-35°C to +90°C
PM, FF, HH or QM
FVMQ
-60°C to +155°C
PF or QF
FEP
-60°C to +180°C
B.8
International
B.8.1
I7 IECEx Intrinsic Safety
Certificate
IECEx FMG 09.0009X
Standards
IEC 60079-0:2017, IEC 60079-11:2011, IEC 60079-26:2014
Markings
Ex ia IIC T4 Ga
Ex ib IIC T4 Ga/Gb
Ta = -50°C to +80°C; IP66, IP67
Ui (Vmax)
Ii (lmax)
Pi
Ci
Li
Entity parameters
30 V
300 mA
1.3 W
1.1 nF
1.5 µH
FISCO parameters
17.5V
380 mA
5.32 W
1.1 nF
1.5 µH
Specific Conditions for Safe Use (X):
1. The enclosure contains aluminum and is considered to present a potential risk of
ignition by impact or friction. When installed as EPL Ga, care must be taken during
installation and use to prevent impact or friction.
Reference Manual
Product Certifications
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
283
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...