12. Ensure that the gauge is directed at an angle of 45° to the line of sight from the
center of the tank to the wall.
13. Use the marks on the Washer Ball to adjust the gauge so the antenna is inclined
roughly 1.5° towards the center of the tank.
Note
For products with high condensation, such as bitumen, the gauge should be
mounted with 0° inclination in order to achieve maximum signal strength.
A. Marks
B. Plumb line
C. Tank center
D. Incline antenna 1.5° towards tank center
14. Tighten the finger nut.
Installation
Reference Manual
September 2019
00809-0100-5901
58