Configure Calibration Distance using TankMaster
™
WinSetup
The cone antenna extension causes a small offset error that needs to be calibrated away by
adjusting the Calibration Distance parameter.
Procedure
1. Start the Rosemount
™
TankMaster
™
WinSetup configuration software.
2. In the WinSetup workspace, right-click on the device icon.
3. Select
Properties
and open the
Geometry
tab.
4. Enter the appropriate
Calibration Distance
:
•
For a 4-in. cone the calibration distance is about 2 mm for each 100 mm
extension
•
For a 6-in. cone the calibration distance is about 1 mm for each 100 mm
extension
•
For an 8-in. cone the calibration distance is 0
Reference Manual
Installation
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
89