The window is set up as follows:
Field 1:
Here you can define the names of the different smoke detector inputs. There is a max. of 5 smoke
detector inputs available. In this field you can also define the texts to be displayed in the status
messages.
Field 2:
Under ”Status Alarm“ you can define in which status the alarm should be triggered.
Field 3:
Within the time period you preset here, the Room Manager expects to receive a status message
from the smoke detector input. If the Room Manager does not receive a status message within
that preset time, the alarm will be triggered.
Field 4:
Here you can display the names of the RF sensors that have been assigned.
Field 5:
If this option has been activated, the Room Manager will give an acoustic alarm once in a minute
in case the battery of the sensors is low.
Field 6:
This is where you can define what actions should be carried out in case of an alarm.
It is possible to switch on 1 output for an adjustable time period in case of an alarm.
It is also possible to activate the acoustic alarm of the Room Manager for an adjustable time
period.
Summary of Contents for RF System 2.42
Page 1: ...Eaton RF System 2 42 Manual...
Page 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Page 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Page 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Page 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Page 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Page 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Page 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...