214
Eaton RF-System - Help
© 2015 Eaton Electrical Group
Long push at the push-button down
Short push at the push-button down
Switched ON
Switched OFF
Falling below the preset temperature
Exceeding the preset temperature
Humidity value not reached
Humidity value exceeded
How does the routing work?
If you draw a connection from a sensor to an actuator and it is calculated, the MRF program
checks the best connection path based on the scanned reception quality of the devices.
If the reception quality between these two devices is too low to establish a direct connection, the
MRF program tries to find a main supplied device in between the sensor and the target (actuator).
This is the so called “Router”. So that the message can not be sent directly from the sensor to the
target it goes from sensor to router and from router to the target. If the first router doesn
’
t
understand the target a second router has to be found and so on…
So in some cases it is possible to need more than one router.
Specific termination of the commands when routing:
1. Sensor send command (sensor to target-actuator) to the router
2. Router acknowledges the command to the sensor (or when the sensor is a router…)
3. Router sends the command (Sensor to target-actuator) to the target-actuator (or to the next
router…)
4. Target-actuator acknowledges to the router and executes the command
When clicking right on a connection and “Show routing” the following is shown:
Summary of Contents for RF System 2.42
Page 1: ...Eaton RF System 2 42 Manual...
Page 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Page 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Page 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Page 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Page 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Page 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Page 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...