status message of the actuator will also be sent if the power value changes according to the
sending frequency slider and the power channel is not connected to other devices.
Load error:
The load error output is a binary output that can be connected to all actuators and inputs of
intelligent devices. It is connected to the power measurement and checks if the actual power value
when the output is switched ON falls below the entered minimum nominal Load. If that is the case
the output will switch to ON (otherwise it’s OFF) as long as this error state is active. If the entered
value is 0 the function is disabled.
Generally we recommend setting the min. load value at least 10% lower than the expected load
value if the output is ON. The output channel will be sent cyclically every 150 minutes independent
of a state change.
Generally like all channels of the energy measurement function the load error output will only be
sent if it has a valid connection to another device.
also see:
Switching actuator 10A/16A - General
Switching actuator 10A/16A – Actuator function
Switching actuator 10A/16A – Binary input
Summary of Contents for RF System 2.42
Page 1: ...Eaton RF System 2 42 Manual...
Page 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Page 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Page 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Page 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Page 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Page 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Page 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...