64
Eaton RF-System - Help
© 2015 Eaton Electrical Group
modifications into the device.
Cancel: Discards the modifications carried out and returns to the MRF main window.
Info: Opens the Help dialog for Switching Actuators
4. The functions bar enables you to select the different functions which the shutter actuator carries
out when it receives a specific command. For each sensor there is a standard function which the
actuator defines after establishing the connection to a sensor (same as in Basic Mode). Some
functions occupy more than just one command button, as we will see in the following function
descriptions:
Among them, depending on the pre-set functions, various slider controls (control time, runtime)
which allow you to set time-related functions.
Shutter actuator with safety functions:
The shutter actuator CJAU-01/02 contains functions to lock the actuator for movement commands.
You can assign 2 safety objects and/or 1 acknowledge object for every shutter actuator.
Safety object:
Every sensor (for example a binary input with a wind or solar sensor) that has been assigned to
the actuator and configured with the function “Safety function when ON” or “Safety function when
OFF”.
Now if the sensor is activated the actuator moves in the safety position (configurable to UP,
DOWN, STOP) and can not be operated by any other sensor. As mentioned above 2 safety
objects can be assigned to each shutter actuator. The safety position has to be the same for both
safety objects. Only when both safety objects are deactivated (if both were activated before) or the
acknowledge sensor is activated the safety function is deactivated.
The interrogation of the release command can be set cyclically. That means a binary input has to
send every 10 minutes a “Safety function deactivated” command to the shutter actuator (if the
actuator is set to 12 minutes). If that is not the case the shutter actuator activates the safety
function automatically after 12 minutes.
Acknowledge sensor:
This sensor can deactivate a safety function independent from the status of the safety objects. For
example if you want to manually operate an actuator.
Configuration window for safety function:
Summary of Contents for RF System 2.42
Page 1: ...Eaton RF System 2 42 Manual...
Page 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Page 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Page 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Page 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Page 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Page 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Page 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...