Chapter 16 PLC Function Applications
MS300
(High Speed Model)
16-3
16-2 Notes before PLC use
1. The MS300 provides 2 communications serial ports that can be used to download PLC
programs (see figure below).
2. Channel 1 communications format is the same as channel 2.
3. Channel 2 has a preset communications format of 7, N, 2, 9600, ASCII can be changed in
Pr. 09-01 (transmission speed) and Pr. 09-04 (communication protocol).
4. The PLC preset is node 2; the PLC node can be changed in Pr. 09-35, but this address may not
be the same as the drive's address setting of Pr. 09-00.
SG +
-
SG
SG ND
USB
RS-485
8 1
Channe l 1
Channe l 2
RS-485
MS300
P in 1: Reserved
P in 2: Reserved
P in 3:
_
CAN GND
P in 4:
-
S G
P in 5:
+
S G
P in 6:
Reserved
G ND
P in 7:
_
CAN GND
5. The client can simultaneously access data from the drive and internal PLC, which is performed
through identification of the node. For instance, if the drive node is 1 and the internal PLC node
is 2, then the client command will be
01 (node) 03 (read) 0400 (address) 0001 (1 data item), indicating that it must read the data
in drive Pr. 04-00
02 (node) 03 (read) 0400 (address) 0001 (1 data item), indicating that it must read the data
in internal PLC X0
6. The PLC program will be disabled when uploading/downloading programs.
7. Please note when using WPR commands to write in parameters, values may be modified up to
a maximum of 10
6
times, otherwise a memory write error will occur. The calculation of
modifications is based on whether the entered value has been changed. If the entered value is
left unchanged, the modifications will not increase afterwards. But if the entered value is
different from before, the number of modifications will increase by one.
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...