Chapter 16 PLC Function Applications
MS300
(High Speed Model)
16-40
Command Function
MC/MCR
Connect/release a common series contact
Operand N0~N7
MC is the main control initiation command, and any commands between MC and
MCR will be executed normally. When the MC command is Off, any commands
between MC and MCR will act as follows:
Determination of commands
Description
Ordinary timer
The timing value will revert to 0, the coil will lose
power, and the contact will not operate
Counter
The coil will lose power, and the count value and
contact will stay in their current state
Coil driven by OUT command None receive power
Elements driven by SET, RST
commands
Will remain in their current state
Applications commands
None are actuated
MCR is the main control stop command, and is placed at the end of the main control
program. There may not be any contact commands before the MCR command.
The MC-MCR main control program commands support a nested program structure
with a maximum only 8 levels; use in the order N0-N7, please refer to the following
program:
Ladder diagram:
X0
MC
N0
X1
Y0
X2
MC
N1
X3
Y1
MCR
N1
MCR
N0
X10
MC
N0
X11
Y10
MCR
N0
Command
code:
Description:
LD X0
Load Contact
A
of X0
MC
N0
Connection of N0 common series
contact
LD
X1 Load Contact
A
of X1
OUT
Y0 Drive
Y0
coil
:
LD X2
Load Contact
A
of X2
MC
N1
Connection of N1 common series
contact
LD X3
Load Contact
A
of X3
OUT Y1
Drive
Y1
coil
:
MCR
N1
Release N1 common series contact
:
MCR
N0
Release N0 common series contact
:
LD X10 Load Contact
A
of X10
MC
N0
Connection of N0 common series
contact
LD X11
Load Contact
A
of X11
OUT Y10 Drive
Y10
coil
:
MCR
N0
Release N0 common series contact
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...