Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-14-5
M anual reset
Ma nual reset
Output cu rrent
Over-torque
de tection level
14-75 (14 -78)
M ulti-function
output terminal
= 73 or 74
Over-torque
detectio n tim e
14-76 (14-7 9)
Electronic Thermal Relay Selection 3 (Motor 3)
Electronic Thermal Relay Selection 4 (Motor 4)
Factory Setting:
2
Settings 0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disabled
In order to prevent the self-cooling motor occurs motor overheating during low speed operation,
users can set the electronic thermal relay to limit the drive output power allowable.
The setting 0 is suitable for inverter motor (with external forced cooling). There is no obvious
correlation between the heat dissipation capability and speed of motor, so the low speed
electronic thermal relay is fixed, it can ensure that the load capacity of the motor at low speed.
The setting 1 is suitable for standard motor (motor with fan on the shaft). The cooling capacity of
motor is poor at low speed, so the electronic thermal relay action time will be appropriate to
reduce, it can ensure the life of the motor.
When power ON/OFF uses frequently, the thermal relay protection will be reset when power
OFF, so even if the setting is 0 or 1, it may not be protected. If there are several motors
connected to a drive, please install the electronic thermal relay in each of motors.
Electronic Thermal Relay Action Time 3 (Motor 3)
Electronic Thermal Relay Action Time 4 (Motor 4)
Factory
Setting:
60.0
Settings 30.0~600.0 sec.
Electronic thermal relay is according to the motor 150 % rated current value and with Pr. 14-81
settings, the settings of Pr. 14-83 is to protect the motor to avoid burned due to motor
overheating. When it reaches the setting time, the drive will display "EoL3 / EoL4", and the
motor will be free run to stop.
This parameter function is based on the operating characteristic curve of electronic thermal
relay I2t, it is according to the drive output frequency, current and running time to protect the
motor and prevent the overheating of motor.
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...