Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-02-3
6: JOG operation (By KPC-CC01 or external control)
7: Acceleration / deceleration speed not allow
8: The 1
st
, 2
nd
acceleration / deceleration time selection
9: The 3
rd
, 4
th
acceleration / deceleration time selection
10: EF input (Pr. 07-20)
11: B.B input from external (Base Block)
12: Output stop
13: Cancel the setting of the auto acceleration / deceleration time
15: Rotating speed command from AVI
16: Rotating speed command from ACI
18: Forced to stop (Pr. 07-20)
19: Digital up command
20: Digital down command
22: Clear counter
23: Input the counter value (MI6)
24: FWD JOG command
25: REV JOG command
28: Emergency stop (EF1)
29: Signal confirmation for Y-connection
30: Signal confirmation for
-connection
38: Disable write EEPROM function
40: Force coast to stop
41: HAND switch
42: AUTO switch
49: Drive enable
50: Master dEb input
51: Selection for PLC mode bit 0
52: Selection for PLC mode bit 1
53: Trigger CANopen quick stop
56: Local / Remote Selection
81: Zero point position signal input of simple positioning
83: Multi-motors (IM) selection bit 0
84: Multi-motors (IM) selection bit 1
This parameter selects the functions for each multi-function terminal.
When Pr. 02-00 = 0, multi-function options can be set by multi-function input terminal MI1, MI2.
When Pr. 02-00
≠
0, specify the use of multi-function input terminals MI1, MI2 with reference to
the setting value of Pr. 02-00.
Example:
If Pr. 02-00 = 1: multi-function input terminal MI1 = FWD / STOP,
multi-function input terminal MI2 = REV / STOP.
If Pr. 02-00 = 2: multi-function input terminal MI1 = RUN / STOP,
multi-function input terminal MI2 = FWD / REV.
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...