Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-06-18
LvX Auto Reset
Factory Setting: 0
Settings 0: Disable
1: Enable
Pr. 06-49=0: Disable; LvA, Lvd, Lvn error will be record and need to be reset.
Pr. 06-49=1: Enable; LvA, Lvd, Lvn error will be record. The DC-BUS voltage has reach Lv reset
level and the Soft-start Relay has turn ON, the Lvx error will be reset automatically.
Treatment for the Detected Input Phase Loss (OrP)
Factory Setting: 0
Settings 0: Warn and ramp to stop
1: Warn and coast to stop
Drive executes input phase loss protection according to Pr. 06-53.
Derating Protection
Factory Setting: 0
Settings 0: Constant rated current and limit carrier wave by load current and
temperature
1: Constant carrier frequency and limit load current by setting carrier wave
2: Constant rated current (same as setting 0), but close current limit
Allowable max. output frequency and the min. carrier wave limit in control mode:
VF: When max. output frequency is 1500.0 Hz, the min. carrier wave is 6 k.
Setting 0:
When the operating point is greater than the derating curve (when the operating carrier
wave is greater than the rated carrier wave), the rated current is constant, and carrier frequency
(Fc) outputted by the drive will auto decrease according to ambient temperature, overload
output current and overload time. If overload situation is not frequent and only cares the carrier
frequency operated with the rated current for a long time, and can accept the change of carrier
wave due to short overload, it is recommended to set to 0. Refer to the following derating curve
for the level of carrier frequency.
For example: ambient temperature 50 °C, UL open-type, and independent installation.
When the carrier frequency is set to 12 kHz, corresponding to 65 % rated output current. (Refer
to the following derating curve)
When output current is higher than the value, it will auto
decrease the carrier wave according to ambient temperature, output current and overload time.
If the output current is 85 % of rated current, the carrier will be reduced to 8 kHz, therefore
the current must operate in 65 % of rated current to maintain the carrier at 12 kHz. Overload will
also reduce the carrier. For example: the carrier is 12 kHz, the current overload capacity is
150 % * 65 % of rated current for 1 minute, if the current is over 150 % * 65 % of rated current, it
will automatically reduce the carrier according to the current and the length of overload time and
other information. The minimum reduce to preset carrier 8 kHz. In addition, the overcurrent stall
prevention function Pr. 06-03 and Pr. 06-04 still retain the current limit for the derating ratio*set
value of Pr. 06-03 and Pr. 06-04.
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...