Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-00-6
When Pr. 00-10 = 0 and set Pr. 00-11 to 0, the V/F control diagram is shown as follows:
Fcmd
Pr. 00-20
AV R
07-23
Ir ms
M
IGB T
P WM
01-00
01-01
01-02
05-01
05-02
05-03
05-04
DC BUS
V /F
table
Voltage
Detection
Protection
Accel. / Decel. time
DC B US Voltage
Cur r ent Detection
01-00,01-01
01-02,01-03
01-04,01-05
01-06,01-07
01-08
Torque
Compensation
LPF
07- 24
07-26
Compensation
voltage
X
+
+
Load Selection
Factory Setting: Ready only
Settings 1: Heavy load
Heavy duty: over load rated output current 200 % in 3 seconds. (150 %,1 minutes) Please refer to
Pr. 00-17 for the setting of carrier wave. Refer to Pr. 00-01 or specification table for the rated
current.
In Heavy Duty, the default setting of Pr. 06-03 and Pr. 06-04 is 180 %, maximum is 200 %.
However, if DC voltage is higher than 700 VDC (460V series) or 350V (230V series), then the
maximum will be 165 %
Carrier Frequency
Factory Setting: 6
Settings Heavy load: 2~15 KHz
This parameter determinates the PWM carrier frequency of the AC motor drive.
Series 230V
460V
Models
1~15HP
[0.75~11kW]
20~30HP
[15~37kW]
1~20HP
[0.75~15kW]
25~40HP
[18.5~55kW]
Settings Range
02~15kHz 02~10kHz 02~15kHz 02~10kHz
Heavy Duty
Factory Setting
6 kHz
2 kHz
8 kHz
15 kHz
Carrier
Frequency
Acoustic
Noise
Electromagnetic
Noise or Leakage
Current
Heat
Dissipation
Current
Wave
Significant
Minimal
Minimal
Minimal
Significant
Significant
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...