Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-02-12
Settings
Functions
Descriptions
8 Over
torque
2
Active when the drive detects over-torque. Pr. 06-10 is for setting
the over-torque detection level (motor 2), and Pr. 06-11 is for
setting over-torque detection time (motor 2).
Refer to Pr. 06-09~06-11.
9
Drive is ready
Active when the drive is ON with no abnormality detected.
10
Low voltage warn (LV)
Active when the DC Bus voltage is too low.
(refer to Pr. 06-00 low voltage level)
11
Malfunction indication
Active when fault occurs (except Lv stop).
13 Overheat
Active when IGBT or heat sink overheats to prevent OH turn off
the drive. (refer to Pr. 06-15)
14
Software brake signal
indication
Active when the soft brake function is ON. (refer to Pr. 07-00)
17
Count value attained
(Pr. 02-20)
When the drive executes external counter, this contact will active
if the count value is equal to the setting value of Pr. 02-20. This
contact will not active when the setting value of Pr. 02-20 > Pr.
02-19.
18
Count value attained
(Pr. 02-19)
When the drive executes external counter, this contact will active
if the count value is equal to the setting value of Pr. 02-19.
19
External interrupt B.B.
input (Base Block)
Active when external interrupt (B.B.) stop output occurs in the
drive.
20
Warning output
Active when the warning is detected.
21
Over-voltage warning
Active when the over-voltage is detected.
22
Over-current stall
prevention warning
Active when the over-current stall prevention is detected.
23
Over-voltage stall
prevention warning
Active when the over-voltage stall prevention is detected.
24 Operation
source
Active when the source of operation command is controlled by
digital keypad. (Pr. 00-21 = 0)
25
Forward command
Active when the operation direction is forward.
26
Reverse command
Active when the operation direction is reverse.
29
Output when frequency
≥
Pr. 02-34
Active when frequency is
≥
Pr. 02-34.
(Actual output H
≥
Pr. 02-34)
30
Output when frequency
< Pr. 02-34
Active when frequency is < Pr. 02-34.
(Actual output H
<
Pr. 02-34)
31
Y-connection for the
motor coil
Active when Pr. 05-24 = 1, frequency output is lower than Pr.
05-23 minus 2 Hz, and time is longer than Pr. 05-25.
32
△
-connection for the
motor coil
Active when Pr. 05-24 = 1, frequency output is higher than Pr.
05-23 plus 2 Hz, , and time is longer than Pr. 05-25.
33
Zero speed (actual
output frequency)
Active when the actual output frequency is 0.
(the drive should be in RUN mode)
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...