Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-00-7
From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise. Therefore, if
the surrounding noise is greater than the motor noise, lower the carrier frequency is good to
reduce the temperature rise. Although it is quiet operation in the higher carrier frequency, the
entire wiring and prevention of interference should be considered.
When the carrier frequency is higher than the factory setting, must decreasing the carrier
frequency to protect the drive. Refer to Pr. 06-55 for the related setting and details.
PLC Command Mask
Factory Setting: Read Only
Settings bit 0: Control command forced by PLC control
bit 1: Frequency command forced by PLC control
This parameter determines if frequency command or control command is locked by PLC.
Source of the Master Frequency Command (AUTO)
Factory Setting: 0
Settings 0: Digital keypad
1: Communication RS-485 input
2: External analog input (Refer to Pr. 03-00)
3: External UP / DOWN terminal
6: CANopen communication card
7:
Digital keypad dial
8: Communication card (not includes CANopen card)
[Note]: Need to use with MO setting as 42, or use with KPC-CC01
The AUTO / HAND mode can be switched by the keypad KPC-CC01 (optional) or multi-function
input terminal (MI) to set the source of the master frequency.
Pr. 00-20 and Pr. 00-21 are for the settings of frequency source and operation source in AUTO
mode. Pr. 00-30 and Pr. 00-31 are for the settings of frequency source and operation source in
HAND mode.
The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal
used to switch AUTO / HAND mode, the highest priority is the multi-function input terminal. When
the external terminal is OFF, the drive will not accept any operation signal and cannot execute
JOG.
Source of the Operation Command (AUTO)
Factory Setting: 0
Settings 0: Digital keypad
1: External terminals
2: Communication RS-485 input
3: CANopen communication card
5: Communication card (not includes CANopen card)
[Note]
:
Need to use with MO setting as 42, or use with KPC-CC01
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...